Eaton Bussmann Authorized Distributor | Certificate No. 56 | Valid Through: December 31, 2026

Photovoltaic Fuses

gPV fuses and holders for solar strings, combiners and inverters, with DC ratings up to 1500 V on selected catalog numbers.

1 product

Selection guide

How to specify a photovoltaic fuse

01

Where gPV fuses are used

Bussmann photovoltaic fuses protect DC strings, combiner boxes and inverter inputs. Selected catalog numbers are rated up to 1500 Vdc and follow UL 248-19 and IEC 60269-6, utilization category gPV.

02

Size for the sunny-day current

The fuse is sized for the string short-circuit current, which is higher than the operating current and can last for hours in full sun. A typical factor is 1.56 on Isc, then check temperature derating inside the combiner.

03

The holder is part of the listing

A 1000 Vdc or 1500 Vdc fuse needs a holder listed for that voltage. A 600 V AC fuse block is not a photovoltaic holder. Order the fuse and the holder together when the combiner is being built.

Buyer questions

Questions buyers ask

What is a gPV fuse?

It is the photovoltaic utilization category. The fuse must interrupt DC fault current at the string or array voltage.

Can I use a 600 V AC fuse on a 1000 V string?

No. The DC voltage rating of the fuse and the holder must be at least the maximum array voltage.

How is the amp rating chosen?

Above the string short-circuit current, then derated for the combiner temperature.

Online RFQ Inquiry

Fill in your requirements. Our engineer will provide a quotation within 1 working day.
Bulk inquiry with BOM list is supported.